Sound transmission loss assessments for dop test acoustic room
NV Dynamics was commissioned by IEPCC Solutions Pvt Ltd to conduct a comprehensive acoustic assessment at Micron Technology located in Sanand, Ahmedabad, Gujarat. The study was undertaken to evaluate the sound isolation performance of a drop-test acoustic room and its adjoining spaces.
The assessment included Sound Transmission Class (STC) testing, Reverberation Time (RT60) measurements, Real-Time Noise Analysis (RTA) and near-field sound pressure level measurements across the common partition systems. Airborne sound transmission measurements were conducted in accordance with ASTM E336-25A, using calibrated Type-1 sound level meter. STC assessments were performed between the drop-test acoustic room and the observer room, as well as between the acoustic room and the common corridor.
Near-field measurements were additionally conducted to identify potential acoustic leakage paths within the separating assemblies. The assessment indicated that the Double-Glazed Unit (DGU) and entry door were significant contributors to noise transmission, thereby affecting the overall sound isolation performance of the room.
The study provided a quantitative assessment of the existing acoustic performance and identified key elements requiring attention for improving the sound isolation of the drop-test acoustic room.