Vibration testing bangalore , Vibration analysis bangalore ,Ground vibration  bangalore , Structural vibration bangalore , Noise analysis bangalore , Dynamic balancing bangalore , Condition monitoring bangalore , Room acoustics bangalore ,Vibration testing india, Vibration analysis india, Ground vibration  india, Structural vibration india, Noise analysis india, Dynamic balancing india, Condition monitoring india, Room acoustics india ,Vibration testing , Vibration analysis,Ground vibration , Structural vibration , Noise analysis,Dynamic balancing , Condition monitoring , Room acoustics , Noise and Vibration Consultants in India , Noise and Vibration Testing Services India, Environmental Noise Testing Services India, Vibration Monitoring Services India, Ground Vibration Assessment India, Construction Vibration Monitoring India, Industrial Noise Measurement Services, Acoustic Consultant India, Metro Rail Noise and Vibration Consultant, Railway Noise and Vibration Assessment, Metro Rail Vibration Monitoring India, Ship Noise Measurement Services, IMO Noise Compliance Testing, Vibration Testing for Semiconductor, Equipment Installation, Data Centre Vibration Assessment

Ground-borne vibration assessment for a semiconductor cleanroom facility



NV Dynamics conducted a comprehensive ground-borne vibration assessment for a proposed greenfield semiconductor cleanroom facility in Bhubaneswar, Odisha. The study was undertaken to establish baseline ground vibration conditions and evaluate the site’s suitability for vibration-sensitive semiconductor and advanced-technology equipment.

The assessment involved vibration measurements at 50 locations distributed across the proposed development area. Ultra-low-frequency, seismic-grade vibration transducers were deployed in three orthogonal directions (X, Y and Z) to capture ground vibration characteristics under ambient conditions. In addition to ambient measurements, controlled truck movement assessments were carried out along the adjacent road to site and the proposed internal road of the facility. Loaded trucks of approximately 35 tonnes were operated at controlled speeds, with multiple scenarios including back-to-back passes, opposite vehicle movements and emergency braking. These conditions were considered to assess potential vibration impacts associated with heavy vehicle movements.

The recorded vibration data was processed in 1/3rd octave bands over the frequency range of 1–80 Hz and evaluated against VC-B and VC-C vibration criteria in accordance with IEST-RP-NANO201.1:2024. The study provides valuable baseline vibration data for the planning and design of the proposed semiconductor cleanroom facility, helping support informed decisions related to vibration-sensitive equipment, facility layout, structural design and cleanroom infrastructure.



Back To Projects